Augos Energy / How we deploy

Metering rollouts for multisite portfolios

From order to live data, site by site.

Each measurement point is assessed from a phone, installed by a qualified electrician with the installer app guiding the job, checked live before activation and recorded on a job card. Live minutes after installation.

Augos is the energy back office for multisite businesses in South Africa: energy management software, bill verification and independent advisers, checking what every site should pay against the meter and the tariff.

The film · 1:10

From a photo to a live meter.

How a rollout runs at every site: assess, quote, ship, install.

Start an assessment ›
Watch the 70 second film: how a rollout runs, from a photo to a live meter.
Read the transcript

Metering a site usually takes three visits from a specialist. One to look, one back to quote, and one more to install. Every visit means traffic, site access, and days of waiting. Augos takes the visits out.

Assess

Assess. Your own team, or the electrician you already use, photographs the board and checks the mobile signal. Nothing a site visit would see is missed.

Quote

Quote. Priced from the photos, the same business day, with the right kit first time.

Ship

Ship. The meter arrives ready to fit.

Install

Install. Your electrician fits it, at their normal rate. The Augos installer app checks the wiring, so there's no second visit. Live in minutes, with a job card for every site. Lower cost to deploy. Faster rollouts. No IT network to connect. One standard at every site. From Johannesburg, Cape Town and Durban, to every province, and across our borders.

Assess. Quote. Ship. Install. Start your first assessment today, at augos.co.za.

The process

Six steps for every site.

1 · Assess

Self-assessment

A qualified person photographs the point from a phone: breaker, CTs, placement and signal, GPS-pinned. No contractor visit to quote.

2 · Order

Works order and quote

The assessment becomes the works order, the material list and the quote, sized CT included, tied to the site's record.

3 · Install

Guided installation

Your own technician or usual contractor fits the meter, with the installer app guiding each step and a wiring diagram for the connection.

4 · Check

Live checks before activation

Voltage, current, polarity, phase rotation, power factor and signal on the live readings. A blocking check stops activation.

5 · Configure

Over the air

The CT and VT ratios go to the meter over the mobile network. No site visit to change a setting.

6 · Record

Job card

Photos, data checks, notes, time stamp and GPS, emailed on activation and kept for the life of the installation.

The installer app

The electrician's phone does the commissioning.

A free web app, added to the home screen from installer-app.augos.io. It scans the device, sets it up, reads the live data back and will not let a wrongly wired meter go live.

Augos installer app: installation type and the safety and liability acknowledgement
AcknowledgeQualified and authorised, before the job clock starts.
Augos installer app: the CT ratio sent to the meter and acknowledged
ConfigureThe CT ratio read off the CT, sent to the meter.
Augos installer app: live readings with every check passing
CheckLive readings, judged against the connection type.
Augos installer app: the six installation photos
RecordSix photos, then the job card goes out.

For your electrician

A first Augos install, in four minutes.

The real installer app screens, narrated, with subtitles for watching on site with the sound off. Send it to your electrician before their first job.

Checked before it goes live

A wrongly wired meter cannot activate.

Some wiring faults make every kWh wrong and cannot be corrected afterwards. The app looks for them on the live readings and blocks activation until they clear, with numbered steps to fix them.

  • Phase rotation detected. A phase's current is on another phase's voltage. The app names the pair to swap.
  • CT reversed on a phase. One CT is facing the wrong way.
  • CT wiring fault on a medium-voltage delta connection: a CT reversed, on the wrong phase or open.
  • CT and VT ratios confirmed by the meter, so power is not under-reported 60 times on a 6600:110 VT.

The record

A job card for every installation.

Emailed the moment the device activates, and kept for the life of the installation: the reference when a bill is disputed, a meter is moved or a CT is replaced. These are real job cards from real sites, with the photos the electrician took.

MeasuredReal installation · LV star · 16 Oct 2026
Measurement pointMain incomer, plastics factory
Started · completed16:15 · 16:23
Connection · CT ratioLV star · 800:5
Cellular signal31 · Good/Excellent
Frequency49.87 Hz
ChecksAll pass
Photos6 of 6
Live readingPhase APhase BPhase C
Voltage231.53 V232.27 V231.33 V
Current18.02 A36.29 A16.82 A
Power3.672 kW8.358 kW3.826 kW
Power factor0.880.990.98
Voltage leads connected at the supply
Voltage leads
Augos Electricity Meter top terminals, wired
Meter terminals
Cellular antenna placed outside the panel
Antenna placement
The distribution board with the meter installed
DB board

Augos installer app, job card of a real installation at a live site, 16 Oct 2026

MeasuredReal installation · LV star · 17 Oct 2026
Measurement pointTransformer mains, industrial site
Started · completed09:14 · 09:21
Connection · CT ratioLV star · 1600:5
Cellular signal25 · Good/Excellent
Frequency50.14 Hz
ChecksAll pass · low power factor flagged on phases B and C
Photos6 of 6
Live readingPhase APhase BPhase C
Voltage229.83 V228.70 V229.87 V
Current55.14 A54.32 A55.10 A
Power9.295 kW6.570 kW7.623 kW
Power factor0.730.530.60
Current transformer on the transformer mains
CT ratio
Augos Electricity Meter showing the power factor on its display
Meter, live
Cellular antennas placed on top of the panel
Antenna placement
The switch room
Switch room

Augos installer app, job card of a real installation at a live site, 17 Oct 2026

Water, the same way.

An Augos Pulse reads a water meter's pulse output. Before handover the app checks that the pulse constant matches on the meter and the device, and that the device reports the dial reading back.

MeasuredReal installation · Augos Pulse on a water meter · 13 Oct 2026
Measurement pointMunicipal water meter, office campus
Started · completed12:24 · 12:58
Pulse constant, meter · device100 L/pulse · 100 L/pulse
Dial reading · device total623.0 kL · 623.3 kL
Battery3.60 V, healthy
Signal-77 dBm, good
ChecksTransmission verified on site
Photos5 of 5
Water meter face and nameplate
Meter nameplate
Water meter dial reading at handover
Dial reading at handover
Augos Pulse strapped to the pipe beside the meter
Augos Pulse mounted
The municipal water meter installation on site
Installation overview

Augos installer app, job card of a real Augos Pulse installation at a live site, 13 Oct 2026

Who does what

Local installers, one standard.

Your electrician

A qualified electrician: your own technician or the contractor you already use. Responsible for the wiring and workmanship, paid at their contracted rate.

Augos

Responsible for the hardware. The energy desk is on the phone in office hours and reviews every installation's photos and data afterwards.

The app

Guides the job, checks the live readings, blocks what cannot be fixed later, and writes the record. The same standard at every site.

Free site assessment

Assess your measurement point and get a quote.

Tell us the site type, supply size and number of sites, photograph the measurement point, and we quote. Electricity now; water, gas and fuel next.

What it costs

One price per meter.

R450 a month per meter, ex VAT, covers every module. Installation is by your electrician, at their contracted rate.

Questions

Who installs the meters?

A qualified electrician: your own on-site technician or the contractor you already use for electrical work. The Augos installer app guides the job, so no specialist Augos technician needs to travel to site.

Who is responsible for what?

Augos is responsible for the hardware. The installer is responsible for the wiring and workmanship, and is paid by you at their normal rate.

How do you know an installation is right?

The installer app checks the meter's live readings before activation: voltage, current, polarity, phase rotation, power factor, frequency and signal. Faults that would make every reading wrong block activation until they are fixed, and the app shows the steps.

What does the electrician need before going to site?

The installer app on the phone's home screen (installer-app.augos.io, in Safari or Chrome), the CT ratio from the CT label, mobile signal at the board, and the site's own isolation and permit rules. The four-minute guide on this page covers the rest.

What record do we get?

A job card for every installation, emailed on activation: photos, the data checks, notes, a time stamp and GPS co-ordinates, kept on record for when the installation changes later.

How soon is a site live?

Minutes after installation. The meter is identified, checked and activated in the same visit.

Can we roll out across many sites and countries?

Yes. Every device lands on the same platform and the same measurement hierarchy, wherever it is installed.

Plan a rollout across your sites.

Step 1 of 3 · Your details